Application |
Staging Equipment (RTU/HP) |
Brand |
Schneider Electric |
Color Casing |
11 - White and White |
Communication |
BACnet |
Communication |
Modbus |
Communication |
Zigbee Pro |
Dehumidification Setpoint Range |
30 to 95 RH |
Dimensions Depth |
2.5 cm (1 in) |
Dimensions Height |
12 cm (4.72 in) |
Dimensions Weight |
0.75 lb (0.34 kg) |
Dimensions Width |
8.6 cm (3.38 in) |
Economizer |
No |
Humidity Control |
Yes |
Humidity Sensor and Calibration |
Single point calibrated bulk polymer type sensor |
Humidity Sensor Precision |
Reading range from 10 to 90 RH noncondensing; 10 to 20 precision is 10; 20 to 80 precision is 5; 80 to 90 precision is 10 |
Humidity Sensor Stability |
Less than 1.0 yearly, typical drift |
Input Binary |
2 |
Input Universal |
5 |
Input Universal Type |
0 to 10 VDC |
Input Universal Type |
10k Thermistor |
Input Universal Type |
Binary |
Interface |
Commercial |
Interface |
Lodging/Hotel |
Interface |
Standard |
Operating Humidity |
0 to 75% RH non-condensing |
Operating Temperature |
0 to 50 C (32 to 122 F) |
Output Binary |
5 |
Output Binary Type |
1A (in-rush 3A) |
Output Universal |
4 |
Output Universal Type |
0 to 10 VDC (5mA max) |
Output Universal Type |
Binary Optomos 0.3A (in-rush 1.5A) |
PIR Cover |
No |
Power Input Frequency |
50 Hz |
Power Input Frequency |
60 Hz |
Power Input Tolerance |
Plus or minus 15% |
Power Input Voltage |
24 VAC |
Product Family |
SE8000 |
Product Series |
SE8600 |
Scheduling |
Yes |
Setpoint Range Cooling |
12 to 37.5 C (54 to 100F) |
Setpoint Range Heating |
4.5 to 32 C (40 to 90 F) |
Standards EMC |
EMC Directive 2004/108/EC |
Standards EMC |
FCC 15 Subpart B |
Standards EMC |
ICES-003 |
Standards EMC |
IEC 61326-1:2005 |
Standards Radio |
CSA C22.2 No. 24-93 |
Standards Radio |
EN 60950-1:2006/A2:2013 |
Standards Radio |
LVD Directive 2006/95/EC |
Standards Radio |
UL 873 |
Standards Safety |
ESTI EN 300 328 V1.8.1 |
Standards Safety |
ESTI EN 301 328 V1.8.1 |
Standards Safety |
ESTI EN 301 489-1 V1.9.2 |
Standards Safety |
FCC 15 Subpart C |
Standards Safety |
R and TTE Directive 1999/5/EC |
Standards Safety |
RSS 210 |
Storage Humidity |
0 to 75% RH non-condensing |
Storage Temperature |
-30 to 50 C (-22 to 122 F) |
Temperature Accuracy |
Plus or minus 0.5 C ( Plus or minus 0.9 F) at 21 C (70 F) typical calibrated |
Temperature Display Range |
-40 to 50 C (-40 to 122 F) |
Temperature Proportional Band |
Cooling and Heating default 1.8 C (3.2 F) |
Temperature Sensor Onboard |
Local 10 K NTC type 2 thermistor |
Temperature Sensor Resolution |
Plus or Minus 0.1 C (Plus or Minus 0.2 F) |
Temperature Sensor Type |
Local 10 K NTC type 2 thermistor |
Wire Gauge |
16 gauge maximum, 22 gauge recommended |